Operating conditions of miniature circuit breakers
Leave a message
1. The upper limit of the ambient air temperature shall not exceed +40℃, and the lower limit shall not be lower than -5℃, and the average temperature over 24 hours shall not exceed +35℃;
Note 1: For working conditions with a lower limit of -10℃ or -25℃, the user must declare this to the manufacturer when ordering;
Note 2: For working conditions with an upper limit exceeding +40℃ or a lower limit below -25℃, the user should consult with the manufacturer.
2. The altitude of the installation site shall not exceed 2000m;
3. The relative humidity of the atmosphere shall not exceed 50% when the ambient air temperature is +40℃. Higher relative humidity is permissible at lower temperatures, such as 90% at +20℃. Appropriate measures should be taken to address occasional condensation due to temperature changes;
4. Pollution level: Level 2;
5. Installation category: Class II and Class III;
6. The external magnetic field of the installation site shall not exceed 5 times the geomagnetic field in any direction;
7. Generally, vertical installation is permitted, with a tolerance of 2° in any direction;
8. The installation site shall be free from significant impact and vibration .