Instructions for using residual current circuit breakers

(1) Residual current devices (RCDs) are suitable for low-voltage power distribution systems where the neutral point of the power supply is directly grounded or grounded through a resistor or reactance. RCDs are not suitable for systems where the neutral point is not grounded. This is because the latter cannot form a leakage electrical circuit; even if a ground fault occurs, generating a current greater than or equal to the rated operating current of the RCD, the RCD cannot trip and cut off the power circuit in time. Alternatively, it may rely on a human body to connect to the fault point to form a leakage electrical circuit, causing the RCD to trip and cut off the power circuit. However, this is still unsafe for the human body. Clearly, a grounding device is necessary. When electrical equipment leaks current, and the leakage current reaches the operating current, the circuit breaker can trip immediately within 0.1 seconds, cutting off the main power circuit.

 

(2) The neutral conductor N of the circuit protected by the RCD must pass through a zero-sequence current transformer. Otherwise, an unbalanced current will cause the RCD to malfunction after connection.

 

(3) The protective earth (PE) conductor must not pass through a zero-sequence current transformer. Because when the protective earth (PE) line passes through the zero-sequence current transformer, the leakage current returns through the PE line to the zero-sequence current transformer, causing current cancellation, and the transformer cannot detect the leakage current value. In the event of a fault, this causes the residual current device (RCD) to fail to operate and thus fails to provide protection.

 

(4) The neutral line of the control circuit cannot be repeatedly grounded. On the one hand, during repeated grounding, under normal operating conditions, a portion of the operating current returns to the power supply neutral point through repeated grounding, resulting in an unbalanced current in the current transformer. When the unbalanced current reaches a certain value, the RCD will malfunction. On the other hand, during a fault leakage, the leakage current on the protective earth line may also return to the power supply neutral point through the neutral line of the current transformer, canceling the leakage current in the transformer and causing the RCD to fail to operate.

 

(5) The neutral line N and the protective earth (PE) line downstream of the RCD cannot be combined into one unit. If the two are combined into one, when a leakage fault or electric shock occurs, the leakage current flows back through the current transformer, resulting in the same situation as (3), causing the leakage current protection device to fail to operate.

 

(6) The wires between the protected electrical equipment and the leakage current protection device must not touch each other. If there is a wire-to-wire contact or a neutral wire-to-neutral wire connection, it will immediately disrupt the zero-sequence balance current value, causing the leakage current protection device to malfunction. In addition, the protected electrical equipment can only be installed in parallel after the leakage current protection device, and the wiring must be correct. The electrical equipment must not be connected to the wiring terminal of the test button.

 

Relevant Standards

1. GB14048.2 Circuit Breakers

2. GB16916.1 RCCB

3. GB16917.1 RCBO

4. GB20044 PRCD

5. GB10963.1 MCB

6. GB6829 General Requirements for Residual Current Devices