Main structure of residual current circuit breaker
Leave a message
Residual current devices (RCDs) possess high sensitivity and rapid action in detecting electric shock and protecting against leakage current, unmatched by other protective electrical appliances such as fuses and automatic switches. Automatic switches and fuses normally carry the load current, and their protection settings must exceed the normal load current; therefore, their primary function is to interrupt phase-to-phase short-circuit faults in the system (some automatic switches also have overload protection). RCDs, however, utilize the residual current of the system for reaction and action. During normal operation, the residual current in the system is almost zero, so its setting value can be set very small (generally in the mA range). When a person experiences electric shock or the equipment casing becomes energized, a larger residual current appears. The RCD detects and processes this residual current and reliably trips to cut off the power supply.
When electrical equipment leaks current, it will present an abnormal current or voltage signal. The RCD detects and processes this abnormal current or voltage signal, causing the actuator to operate. We call residual current devices (RCDs) that operate based on fault current "current-type RCDs," and those that operate based on fault voltage "voltage-type RCDs." Due to their complex structure, poor stability of operating characteristics under external interference, and high manufacturing costs, voltage-type RCDs have been largely phased out. Research and application of RCDs both domestically and internationally are dominated by current-type RCDs.
Current-type RCDs use a portion of the zero-sequence current in the circuit (usually called residual current) as their operating signal. They often use electronic components as intermediate mechanisms, offering high sensitivity and comprehensive functions, thus leading to their increasingly widespread use. A current-type RCD consists of four parts:
1. Detection element: The detection element can be considered a zero-sequence current transformer. The protected phase line and neutral line pass through the toroidal core, forming the primary coil N1 of the transformer. The winding wound around the toroidal core forms the secondary coil N2. If no leakage occurs, the vector sum of the currents flowing through the phase line and neutral line is zero, therefore no corresponding induced electromotive force can be generated in N2. If a leakage current occurs, the vector sum of the currents in the phase and neutral lines will not be zero, inducing an electromotive force (EMF) in N2. This signal will be sent to the intermediate circuit for further processing.
2. Intermediate Circuit: The intermediate circuit typically includes an amplifier, comparator, and trip unit. When the intermediate circuit is electronic, it also requires an auxiliary power supply to provide the power needed for the electronic circuitry to operate. The function of the intermediate circuit is to amplify and process the leakage current signal from the zero-sequence current transformer and output it to the actuator.
3. Actuator: This structure receives the command signal from the intermediate circuit, executes the action, and automatically cuts off the power supply to the fault location.
4. Test Device: Since the leakage current protector is a protective device, its integrity and reliability should be checked regularly. The test device simulates a leakage current path by connecting a test button and a current-limiting resistor in series to check whether the device can operate normally.