Miniature residual current circuit breakers (RCCBs) can be classified according to different standards to adapt to various application scenarios and protection requirements.
Based on the number of poles and wiring method, they can be divided into 2P, 1P+N, 3P, and 4P types. 2-pole RCCBs disconnect both the phase and neutral wires simultaneously, typically used for main or branch protection in single-phase power supply systems. 1P+N RCCBs are widely used in household branch circuits, usually disconnecting only the phase wire. 3-pole RCCBs disconnect all three phase wires simultaneously, used in three-phase three-wire systems. 4-pole RCCBs disconnect all three phase wires and the neutral wire simultaneously, used for main protection in three-phase four-wire systems.
Based on structural form, they can be divided into electromagnetic and electronic types. Electromagnetic RCCBs derive their operating energy directly from the electromagnetic force generated by the residual current itself, requiring no auxiliary power supply, offering high reliability and strong anti-interference capabilities. Electronic RCCBs detect the residual current and control the electromagnetic tripping device through an electronic amplifier, requiring an auxiliary power supply, but offering high sensitivity and are currently the mainstream in the market.
Based on installation method, they can be divided into DIN rail mounted, socket integrated, and portable types. DIN rail mounted RCCBs are the most common, installed on standard DIN rails. Integrated sockets are mounted on wall sockets or portable socket panels. Portable, they resemble plug adapters and are commonly used for temporary power needs.
Based on tripping characteristics, they can be categorized into Type B, Type C, Type D, and Type K. Type B is used for resistive loads. Type C is used for general circuits. Type D is used for high-inrush current loads. Type K is used for motor protection. Intelligent residual current circuit breakers can be configured with either Type C or Type D tripping curves.
Based on residual current operating value, they can be categorized into high sensitivity, medium sensitivity, and low sensitivity. High sensitivity (≤30mA) is mainly used for socket protection in direct contact or high-humidity environments. Medium sensitivity (30mA-100mA) is the most commonly used standard value in homes and offices, providing effective protection against electric shock. Low sensitivity (>100mA) is mainly used for main switches or fire protection.
Based on operating time, they can be categorized into general-purpose, Type S, and high-speed types. General-purpose types are mainly used for main switches in fire protection or upstream switches in graded protection systems, with a longer operating time. The S-type circuit breaker features an intentional time delay and is typically used in main switches to achieve selective tripping in conjunction with downstream switches. The high-speed type is commonly used for terminal equipment protection, with an operating time ≤0.1 seconds when the residual current equals the rated value.
Based on protection function, circuit breakers can be divided into residual current circuit breakers (RCCB) only and residual current circuit breakers (RCBO) with overcurrent protection. RCBO integrates overload and short-circuit protection functions in addition to residual current protection.
Technical Parameters:
1) Rated operating voltage (Ue): AC 230V/400V (1P), 400V (2P, 3P, 4P).
2) Rated insulation voltage (Ui): 600V.
3) Rated impulse withstand voltage (Uimp): 4KV.
4) Rated current (In): 1A, 3A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A. 5) Rated short-circuit breaking capacity (Icn): 6A-40A: 6000A, 50A-63A: 4500A.
6) Operating short-circuit breaking capacity (Ics): 6A-40A: 6000A, 50A-63A: 4500A.
7) Number of poles: a. Single pole (1P); b. Two poles (2P); c. Three poles (3P); d. Four poles (4P).
8) Instantaneous tripping type: a. Type C (5ln-10ln); b. Type D (10ln-16ln).
9) Reference ambient temperature: 30℃.
10) Grid spacing (mm): 6A-40A: 50mm, 50A-63A: 45mm.
11) Enclosure protection rating: IP20. 12) Lifespan: a. Electrical lifespan: not less than 4000 cycles; b. Mechanical lifespan: not less than 20000 cycles.
Operating Conditions
1) Ambient air temperature: upper limit not exceeding +40℃, lower limit not less than -5℃, and 24-hour average temperature not exceeding +35℃;
Note 1: For operating conditions with a lower limit of -10℃ or -25℃, the user must declare this to the manufacturer when ordering;
Note 2: For operating conditions with an upper limit exceeding +40℃ or a lower limit below -25℃, the user should consult with the manufacturer.
2) The altitude of the installation site shall not exceed 2000m;
3) The relative humidity of the atmosphere shall not exceed 50% when the ambient air temperature is +40℃. Higher relative humidity is permissible at lower temperatures, such as 90% at +20℃. Appropriate measures should be taken to address occasional condensation due to temperature changes;
4) Pollution degree: Level 2;
5) Installation category: Class II and Class III;
6) The external magnetic field of the installation site shall not exceed 5 times the geomagnetic field in any direction;
7) Generally, vertical installation is permitted, with a tolerance of 2° in any direction;
8) The installation site shall be free from significant impact and vibration.